Terminal

Storage:

1. Storage Conditions:

The battery should be stored under the following conditions

(1) Low humidity

(2)5 to 122℉ (-15 to 50℃)

(3) Clean and avoid direct sunlight.

2. Capacity after long term storage

After long term storage, all batteries deliver less than rated capacity on cycle. In cyclic application, full capacity may be

obtained through several charge/discharge cycles, typically 3-4 cycles.

3. Refresh Charge

When batteries are placed in extended storage, it is recommended that they receive a refresh charge at recommended

intervals as following:

Storage ambient:              Recommended interval

Below 68℉(20℃)      :          12months

68 to 86℉(20 to 30℃)   :          6months

86 to 104℉(30 to 40℃)  :          3months

Refresh charging method: 12-16 hours of constant voltage of 2.45V/cell

Caution:

Never charge the battery in a sealed container.

Never disassemble the battery.

Never short-circuit battery terminals.

Never incinerate batteries, for they may explode.

Do not press and/or bend the terminals or overheat them.

Do not mix old and new batteries together, neither use batteries of different types or brands.

Do not dispose of with household waste.

Be sure to use the specified charger for battery and follow the charging instructions correctly.

Be sure to charge the batteries between the temperatures 0 to 45℃.

Be sure to position batteries securely, protecting them from abnormal shocks and /or vibration.

Be sure to keep sufficient space between batteries for ventilation (where possible>10mm).

Be sure to install batteries in a cool and well ventilated place.

The surrounding temperature must remain between-20to 40℃ during storage.

Recharge the batteries at least every 6 months during storage.